Picking a backflow preventer really comes down to two questions. Is it just backsiphonage, or could there be backpressure too? And is the hazard low or high? Answer those two and the right device usually jumps out at you.

Here's each type, what it's good for, and the traps exam questions love to set.

Backsiphonage vs backpressure

Backsiphonage is when the supply pressure drops and water gets sucked backward, like drinking through a straw. Backpressure is when something downstream pushes harder than the supply, like a pump or a boiler.

A low hazard means the water might taste or look bad. A high hazard means it could actually make someone sick.

Air gap

An air gap is just open space between the water outlet and the flood level rim of whatever it's filling. It works for any hazard and any kind of backflow. And since there's nothing mechanical, there's nothing to fail.

Atmospheric vacuum breaker (AVB)

An AVB is about as simple as it gets: a body, a checking member, and an air port. It only handles backsiphonage, and it can't stay under constant pressure. Put a shutoff valve downstream of it and it stays pressurized, which means it stops doing its job.

Mount it at least 6 in. above the flood level rim of whatever it serves. The UPC also wants it 6 in. (or its listed distance) above all the piping downstream.

Pressure vacuum breaker (PVB)

A PVB is also backsiphonage only, but it's rated for high or low hazard and it can stay under constant pressure. That's why you see them so much on irrigation systems with zone valves downstream.

It goes at least 12 in. above all the downstream piping and outlets. It can spit some water, so put it where that won't hurt anything.

Heads up for the exam: The word "pressure" in pressure vacuum breaker is about what it can handle, not what it protects against. A PVB is still backsiphonage only. For backpressure you need a double check (low hazard) or an RPZ (high hazard).

Double check assembly (DC)

A double check handles both backsiphonage and backpressure, and it's fine under constant pressure. The catch? It's low hazard only. It looks like it can handle anything, which is exactly why people put it where it doesn't belong.

Reduced pressure assembly (RPZ)

An RPZ has two check valves with a relief valve in between. It covers high or low hazard against both types of backflow, and it can stay under pressure all day.

It dumps water out of its relief port, so install it somewhere a little water won't cause damage. If it's dripping steady, it's either stopping backflow or the first check is dirty. Figure out which. Don't ever plug it.

Cheat sheet

  • Air gap: any hazard, any backflow, nothing to break
  • AVB: backsiphonage only, no constant pressure, 6 in. above the flood rim
  • PVB: backsiphonage only, OK under pressure, 12 in. above downstream piping
  • Double check: both kinds of backflow, low hazard only
  • RPZ: both kinds of backflow, high or low hazard, dumps water
  • Testable assemblies get tested at install, repair, relocation, and at least yearly

Common questions

Which backflow preventer stops backpressure?

A double check for low hazard or an RPZ for high hazard. An air gap works too. Vacuum breakers don't.

Can I put a valve downstream of an AVB?

No. A downstream valve keeps it under constant pressure, and it isn't built for that.

Why is my RPZ dripping?

It's either stopping backflow or the first check is dirty. Check it out, and never plug the relief port.