If your state tests on the International Plumbing Code, this is the practice test for you. Every question below is based on the IPC, and a lot of them cover the spots where the IPC gives a different answer than the UPC.
That matters more than people think. If you studied from a mixed source, some of the numbers in your head may be UPC numbers. Work through these and see which ones catch you.
-
Question 1 of 15
Which of these locations most often needs provision against freezing, despite looking like interior space on a drawing?
Show answerHide answer
Answer: C. Attics, crawl spaces and concealed outside walls
Attics, crawl spaces and cavities in outside walls sit inside the building but outside the heated space, which is exactly why pipe ends up there and then freezes. Protection is by insulation or added heat or both. A heated mechanical room, a heated slab and an interior wall of a heated space are all within the heated envelope.
-
Question 2 of 15
Under IPC Section 316.1.5, what happens where the code official determines that an alternative engineered design conforms to the intent of the code?
Show answerHide answer
Answer: B. The plumbing system shall be approved, and a refusal must be given to the designer in writing with reasons
It SHALL BE APPROVED, and Section 316.1.5 adds that if it is not approved the code official shall notify the registered design professional IN WRITING, stating the reasons. This is where the two codes genuinely diverge on otherwise near-identical sections. The other code makes the approval DISCRETIONARY, says in terms that it has no effect beyond that jurisdiction’s boundaries, and lets the authority order an independent review at the applicant’s expense. Independent review, discretionary approval and an approval confined to the jurisdiction are all that code’s provisions, not this one’s.
-
Question 3 of 15
Under 2024 IPC Table 608.1, how is the backflow preventer for carbonated beverage machines rated?
Show answerHide answer
Answer: B. Low hazard, against backpressure or backsiphonage
Table 608.1 lists the backflow preventer for carbonated beverage machines as low hazard, against backpressure or backsiphonage, in sizes 1/4 in. to 1/2 in., conforming to ASSE 1022. The rating surprises people, and reasonably so: carbonic acid dissolves copper and carbonator backflow has caused documented copper poisoning. It is also a genuine disagreement between the two model codes, because the other one marks the same ASSE 1022 application for contamination as well as pollution. On this track the table governs, and Section 608.17.1.1 separately requires that the piping downstream of the second check valve not be affected by carbon dioxide gas, which is where the code addresses the copper problem.
-
Question 4 of 15
IPC Appendix E computes static loss at 0.433 psi per foot in one place and 0.5 psi per foot in another. What accounts for that?
Show answerHide answer
Answer: C. The 0.433 figure belongs to the segmented calculation and 0.5 is the round-up used with Table E104.1
A foot of water exerts 0.433 psi, and that is the figure the segmented loss method in Section E103.3 uses, because that method accounts for every loss separately and precisely. Section E104.1 sizes from a table instead, where precision of that order is not available anyway, and rounds up to 0.5 psi per foot. Rounding up is conservative: it charges the lift slightly more than it costs and leaves a little in hand. Use the figure belonging to the method you are working in rather than deciding which one is more correct.
-
Question 5 of 15
Under the IPC, where may a potable water service pipe not be located?
Show answerHide answer
Answer: C. In, under or above a septic tank or seepage pit
Potable water service pipes may not be located in, under or above cesspools, septic tanks, septic tank drainage fields or seepage pits. It is a flat prohibition on position relative to those features rather than a separation distance, which is why no number appears in it.
-
Question 6 of 15
Under the 2024 IPC, which document governs the MAINTENANCE AND OPERATIONS of a medical gas system?
Show answerHide answer
Answer: B. The International Fire Code
The INTERNATIONAL FIRE CODE. IPC Section 1201.1 states the split in one sentence: the chapter governs the DESIGN AND INSTALLATION of piping and storage systems for nonflammable medical gas and nonmedical oxygen systems, and ALL MAINTENANCE AND OPERATIONS of such systems shall be in accordance with the International Fire Code. The division is worth holding because it decides who a question belongs to. Putting the system in is plumbing work under a plumbing permit; running and maintaining it afterwards is governed elsewhere, and a plumber asked to service an existing system is no longer working under the chapter that covered the installation.
-
Question 7 of 15
Under the 2024 IPC Chapter 2 definitions, what is a common vent?
Show answerHide answer
Answer: B. A vent connecting at the junction of two fixture drains, or to a fixture branch, and serving as a vent for both fixtures
A vent connecting at the junction of two fixture drains, or to a fixture branch, and serving as a vent for both fixtures. The definition names the connection point, which is why Section 911.2 can then say the vent goes at the interconnection or downstream of it. The vent connecting two or more individual vents is a branch vent, which joins individual vents rather than serving fixtures directly.
-
Question 8 of 15
Under 2024 IPC Section 608.16.1, how must an opening or outlet equipped for a hose connection be protected?
Show answerHide answer
Answer: D. By means other than an air gap
Section 608.16.1 states that openings and outlets equipped for hose connection shall be protected by means other than an air gap. The reason is structural rather than a matter of degree: an air gap is defined between an outlet and the flood level rim of a receiving vessel, and a hose outlet has no fixed receiving vessel. Whatever the hose end reaches becomes the vessel, and it moves. That is why hose outlets are protected by a device, ordinarily a hose connection vacuum breaker, rather than by geometry.
-
Question 9 of 15
Under the footnote to IPC Table 709.1, what effect does a showerhead over a bathtub have on the drainage fixture unit value?
Show answerHide answer
Answer: B. None
None. The footnote states that a showerhead over a bathtub or whirlpool bathtub attachment does not increase the drainage fixture unit value, so the bathtub row of 2 dfu covers it. The reasoning is that a person uses one or the other, not both, so the peak load the drain sees is unchanged by the second outlet being there.
-
Question 10 of 15
An existing building drain runs 4 in. from the stack base and reduces to 3 in. for the last 20 ft before it leaves the building, where the load is unchanged. Under the IPC, what is wrong?
Show answerHide answer
Answer: A. The size of drainage piping shall not be reduced in the direction of flow
Section 704.2 prohibits reducing the size of drainage piping in the direction of flow, and it does so without reference to whether the smaller pipe could carry the load. A reduction presents the flow with a constriction at the point where it is least able to accommodate one, and it creates a place for solids to lodge. The section does list three things that are not treated as reductions, and all three are water closet connection details rather than changes in the carrying capacity of a drain.
-
Question 11 of 15
Under the 2024 IPC, a full-open valve is required at the base of every water riser pipe, but not in certain occupancies. Which ones are excluded?
Show answerHide answer
Answer: D. One- and two-family dwellings, and multiple-family residences two stories or less in height
Item 4 of Section 606.1 requires a full-open valve at the base of every water riser pipe in occupancies other than multiple-family residential occupancies that are two stories or less in height, and other than one- and two-family residential occupancies. The logic is proportionality: in a small building the valve at the entrance to the structure already isolates nearly everything, so a riser valve adds little. In a taller or larger building, isolating one riser instead of the whole building is the difference between a contained repair and a disruption to every tenant. Compare item 5, which requires a valve on the top of every water down-feed pipe and excludes only one- and two-family dwellings.
-
Question 12 of 15
Under the IPC, where three or more drinking fountains are required, what portion may be replaced by water dispensers?
Show answerHide answer
Answer: B. Up to 50 percent
Water dispensers may be substituted for not more than 50 percent of the required number, and only where three or more fountains are required. Restaurants that provide drinking water in a container free of charge are handled separately and need no fountains at all.
-
Question 13 of 15
A system has a temperature-actuated mixing valve and a hot water recirculating pump. Under IPC Section 607.2.3, where shall the hot or tempered water return line be routed?
Show answerHide answer
Answer: D. To the cold water inlet pipe of the water heater, and to the cold water inlet pipe or the hot water return connection of the mixing valve
Section 607.2.3 routes the return to the cold water inlet pipe of the water heater AND to the cold water inlet pipe or the hot water return connection of the temperature-actuated mixing valve. Two connections are needed because there are two things circulating: the loop has to get cooled water back to the heater to be reheated, and the mixing valve has to see return flow so that it keeps controlling the blend rather than sitting dead-headed while the pump runs.
-
Question 14 of 15
Under the IPC, where may slip joints be installed on a trap?
Show answerHide answer
Answer: B. On the inlet, outlet and within the seal
Slip joints are permitted on the trap inlet, the trap outlet and within the trap seal, and must be made with an approved elastomeric gasket. Restricting them to these points keeps them where they are accessible and where a leak shows, rather than buried in concealed pipe. The other model code words its restriction differently and more tightly.
-
Question 15 of 15
Under the 2024 IPC, what does Section 608.14.4 require of a barometric loop?
Show answerHide answer
Answer: A. It precedes the point of connection and extends vertically to a height of 35 ft
Section 608.14.4 requires barometric loops to precede the point of connection and to extend vertically to a height of 35 feet, and states that a loop shall only be utilised as an atmospheric-type or pressure-type vacuum breaker. The figure is not arbitrary. Atmospheric pressure at sea level will support a column of water about 34 feet high, so a loop rising past that cannot be siphoned over its own crest no matter what happens to the supply. It follows that a loop protects against backsiphonage only, which is why the section confines it to vacuum breaker duty.
Missed a few? Check whether they were sizing questions or rule questions. Sizing misses usually mean you need more time in the tables. Rule misses usually mean you picked up a UPC number somewhere.
Not sure which code your state uses? Check with your state licensing board before you study too deep. The code book you are allowed to bring into the exam tells you too.