Backflow questions show up on every plumbing exam because getting it wrong in the field can make people sick. You need to know the difference between backsiphonage and backpressure, and which device protects against which.

This test covers cross connections, air gaps and air breaks, vacuum breakers, and testable backflow assemblies. The big idea in most of these questions is matching the device to the hazard.

  1. Question 1 of 15

    A carbonated beverage dispenser is being connected to the potable supply. Which protection is required, and what else must be checked?

    Show answerHide answer

    Answer: A. A backflow preventer conforming to ASSE 1022 or an air gap, and the piping downstream must not be affected by carbon dioxide

    Both codes name a backflow preventer conforming to ASSE 1022 or an air gap, and both add the same warning about the piping: the IPC says the portion downstream of the second check valve shall not be affected by carbon dioxide gas, and the UPC says the piping installed downstream shall not be affected by it. The warning exists because carbon dioxide dissolved in water makes carbonic acid, which attacks copper and puts dissolved copper into the drink. It is the rare case where selecting the right device is only half the requirement.

  2. Question 2 of 15

    A plumber says a building "has no backflow because nothing has ever come back." What is wrong with that reasoning?

    Show answerHide answer

    Answer: C. Backflow is the event and a cross connection is the arrangement; the second is what gets corrected

    A cross connection is the arrangement; backflow is water actually moving the wrong way through it. Codes regulate the arrangement, because the event is unpredictable and usually invisible. Nobody watches a main break at two in the morning and nobody tastes the difference afterward. That is also why enforcement is written as a prohibition on the connection rather than on the flow: the IPC prohibits cross connections except where approved protection is installed, and the fact that nothing has come back yet is not a defence.

  3. Question 3 of 15

    What is the critical level marking on a vacuum breaker?

    Show answerHide answer

    Answer: A. The reference point for its minimum installed height

    The critical level, marked C-L or C/L, is a reference point established by the testing laboratory and usually stamped on the device, determining the minimum elevation above the flood level rim of the fixture or receptor at which the device may be installed. It exists because the point inside the device that actually governs is not obvious from outside. Both codes add the same fallback: where a device bears no critical level marking, the bottom of the vacuum breaker or combination valve is taken as the critical level, which is the conservative reading.

  4. Question 4 of 15

    Under both codes, indirect waste piping discharges through an air gap or air break into what?

    Show answerHide answer

    Answer: D. A waste receptor, which is itself trapped and connected to the building drainage system

    An indirect waste pipe is one that does not connect directly with the drainage system but discharges into it through an air break or air gap into a trap, fixture, receptor or interceptor. The receptor is a floor sink, standpipe, hub drain or floor drain that receives that discharge, and it is trapped and connected to the drainage system in the ordinary way. The separation removes the continuous path; it does not remove the need to carry the water away properly.

  5. Question 5 of 15

    A heat exchanger uses an essentially toxic transfer fluid. How is the potable water separated from it?

    Show answerHide answer

    Answer: C. By double-wall construction with a space between the two walls open to the atmosphere

    Both codes require double-wall construction with an atmospheric space between the walls: the IPC states that an air gap open to the atmosphere shall be provided between the two walls, and the UPC requires the space between the two walls to be vented to the atmosphere. The vented space is the whole mechanism. A leak in either wall discharges to atmosphere and becomes visible, so transfer fluid cannot reach the potable water without both walls failing at once. Where the transfer fluid is essentially nontoxic, single-wall construction is permitted.

  6. Question 6 of 15

    Why is a potable water outlet that terminates below the rim of the vessel it fills treated as a hazard in its own right?

    Show answerHide answer

    Answer: B. It has no air gap, so a pressure reversal draws the contents of the vessel straight into the piping

    An outlet above the flood-level rim is separated from whatever is below it by a column of air, and air cannot be siphoned up a pipe. Drop the outlet below the rim and that separation is gone: the pipe and the vessel are one continuous body of water, so any reversal of pressure moves the vessel contents into the supply. This is why the air gap is defined as the unobstructed vertical distance through the free atmosphere from the lowest opening of the outlet to the flood-level rim, and why a submerged inlet is the arrangement backflow prevention exists to eliminate.

  7. Question 7 of 15

    A connection is subject to high-hazard backpressure and must stay under pressure continuously. Which assembly covers it?

    Show answerHide answer

    Answer: A. A reduced pressure principle backflow prevention assembly

    Three requirements have to be met together: high hazard, backpressure, and continuous pressure. The reduced pressure principle assembly is the only one that meets all three. Both codes list it for high or low hazard against backpressure or backsiphonage, and it is built to sit under pressure permanently. Each distractor fails on exactly one axis, which is how device selection questions are usually set: the device that is nearly right is more dangerous than the one that is obviously wrong.

  8. Question 8 of 15

    An indirect waste pipe is extended downward so that its outlet finishes about an inch below the rim of the floor sink, though still well above the standing water in it. What has the installer created?

    Show answerHide answer

    Answer: A. An air break, which is a different arrangement from the air gap that may have been required

    Below the flood level rim and above the trap seal is the definition of an air break, so that is what now exists. Whether it is acceptable depends on what the pipe carries: an air break serves clear-water wastes under both codes, and does not serve a discharge for which an air gap was specified. The lesson is that the rim is not a tolerance, it is a boundary, and crossing it converts one named arrangement into another with weaker protection.

  9. Question 9 of 15

    A coffee machine and a carbonated beverage dispenser are both being connected in the same cafe. What differs between them?

    Show answerHide answer

    Answer: B. A dual check backflow preventer is acceptable for the coffee machine but not for the carbonator

    Both codes let a coffee machine or ice maker be protected by a dual check backflow preventer or an air gap, and neither permits a dual check on a carbonator. The reason is the carbon dioxide. A coffee machine receives water and keeps it; a carbonator forces gas into it at pressure, so backpressure is guaranteed rather than hypothetical and the resulting carbonic acid is aggressive to the piping. Same cafe, same wall, two different connections, and the machine that looks more dangerous because it is hot is the one with the lighter requirement.

  10. Question 10 of 15

    A rainwater storage tank on a roof parapet is topped up from the potable supply through a fill line entering below the tank water level. The tank stands about thirty feet above the fill connection and holds only collected rainwater. There is no pump. Assess the hazard and the mechanism.

    Show answerHide answer

    Answer: C. Contamination, a high hazard, by backpressure

    Two judgements, and the hazard one is where people go wrong. Collected rainwater has washed a roof that birds and rodents use, so it carries faecal organisms and whatever the roofing and the air deposit there; public-health guidance on collected rainwater is explicit that untreated roof runoff can carry disease organisms and chemical contamination. Both codes treat it as nonpotable water and require the piping to be identified with DO NOT DRINK marking, which is not how a code speaks about an aesthetic objection. So this is contamination, a high hazard. The mechanism is the interesting half: there is no pump, and the absence of one is what leads people to answer backsiphonage, but a tank standing thirty feet up exerts about thirteen psi of static head at the fill line. Elevation is a pressure source exactly as a pump is, and a fill line entering below the tank water level gives that head somewhere to push.

  11. Question 11 of 15

    Which pair of assemblies has to be installed where a discharge of water would do no harm?

    Show answerHide answer

    Answer: B. The reduced pressure principle assembly and the pressure vacuum breaker assembly

    A reduced pressure assembly relieves through its port whenever the differential falls, and a pressure vacuum breaker spills through its air inlet when the line drains or the check leaks. The UPC table records this in one short phrase per row: may discharge water for both, and does not discharge water for the double check. It decides where a device can go. An assembly that may discharge cannot sit above a finished ceiling or an electrical panel, and the IPC adds that a pressure vacuum breaker must not be installed where spillage could damage the structure.

  12. Question 12 of 15

    What does a drainage air gap measure between?

    Show answerHide answer

    Answer: B. The outlet of the waste pipe and the flood level rim of the receptor below it

    A drainage air gap is the unobstructed vertical distance through the free atmosphere between the outlet of the waste pipe and the flood level rim of the receptor it discharges into. Both ends are fixed features of the installation, which is what makes the gap something you can inspect. Measuring to the water surface would give a number that changes every time the receptor fills, and a gap that disappears the moment it matters most.

  13. Question 13 of 15

    A hot water boiler is fed from the potable supply, and the maintenance contract includes dosing the system with a conditioning chemical. Which protection satisfies both model codes?

    Show answerHide answer

    Answer: C. A reduced pressure principle backflow prevention assembly

    Untreated, a boiler connection is a low hazard and both codes accept a backflow preventer with an intermediate atmospheric vent. Conditioning chemicals change that, and both codes respond the same way: the IPC requires an air gap or a reduced pressure principle backflow preventer, and the UPC requires a reduced pressure principle assembly. So the reduced pressure assembly is the one answer acceptable under either code. Note how little the boiler itself matters to the reasoning; what matters is that somebody adds a chemical to the water on the far side of the connection.

  14. Question 14 of 15

    A lawn irrigation system is fed from the potable supply. Its sprinkler heads sit flush with the soil and retract below grade when the system is off, where they can stand in pooled water carrying lawn fertiliser and animal waste. No injector or pump is fitted. Assess the hazard and the mechanism.

    Show answerHide answer

    Answer: B. Contamination, a high hazard, by backsiphonage

    Water pooling at grade in a lawn carries fertiliser and animal waste, and animal waste spreads disease, so this is contamination, a high hazard. With no injector and no booster pump, nothing in the arrangement can exceed supply pressure, which leaves backsiphonage. A retracted head standing in pooled water is a submerged outlet in every meaningful sense, and it is submerged in the worst thing on the site. This is also why the IPC prohibits potable water outlets and combination stop-and-waste valves below grade, where they cannot be kept clear of standing water.

  15. Question 15 of 15

    An irrigation zone valve sits downstream of the point of protection, so the piping between the two stays pressurised whenever the system is charged. The hazard is high and the only reverse-flow risk is backsiphonage. Which device suits?

    Show answerHide answer

    Answer: C. A pressure vacuum breaker assembly

    The downstream zone valve is the deciding fact. It holds the device under pressure for as long as the system is charged, which rules out every atmospheric-type vacuum breaker regardless of hazard. A pressure vacuum breaker assembly is built for exactly this: both codes list it for high or low hazard, backsiphonage only, and the UPC installation column notes that it may have valves downstream. Since the risk here is backsiphonage alone, a reduced pressure assembly would work but is more device than the situation needs.

0 / 15Answer the questions above to see your score

If you mixed up devices, go back to two questions: is it backsiphonage only, or backpressure too? And is the hazard low or high? Those two answers point you to the right device almost every time.

Remember that local water purveyors often have their own backflow rules on top of the plumbing code.

Want more questions like these?