Trap arm length is just how far your trap can sit from its vent. Go past the limit and the water running down the arm can pull the trap dry. Then you've got sewer gas coming up through the sink.

The annoying part is that the IPC and the UPC don't agree. The IPC gives you distances in feet. The UPC uses inches, and its numbers are shorter. So the exact same trap arm can pass on one code and fail on the other.

So what counts as the trap arm?

It's the stretch of pipe between the trap weir and the vent. The weir is the spot where the water in the trap spills over toward the drain.

Both codes start measuring at the weir. The IPC measures to the vent fitting, and the UPC measures to the inner edge of the vent. Start your tape anywhere else and your number is off.

IPC trap arm lengths

The IPC table is in feet, and every distance comes with a slope. Here's what you get:

  • 1 1/4 in. trap: 5 ft at 1/4 in. per ft
  • 1 1/2 in. trap: 6 ft at 1/4 in. per ft
  • 2 in. trap: 8 ft at 1/4 in. per ft
  • 3 in. trap: 12 ft at 1/8 in. per ft
  • 4 in. trap: 16 ft at 1/8 in. per ft

UPC trap arm lengths

The UPC table is in inches, and it keeps 1/4 in. per ft for every size. You'll notice the numbers are a lot shorter than the IPC:

  • 1 1/4 in. trap arm: 30 in. (2 1/2 ft)
  • 1 1/2 in. trap arm: 42 in. (3 1/2 ft)
  • 2 in. trap arm: 60 in. (5 ft)
  • 3 in. trap arm: 72 in. (6 ft)
Heads up for the exam: Watch the units. A 5 ft arm on a 1 1/2 in. trap is fine under the IPC, since you get 6 ft. Under the UPC it fails, because 5 ft is 60 in. and you only get 42 in.

The UPC has a minimum too

This one surprises people. Under the UPC, the vent can't be too close either. It has to be at least two times the pipe diameter away from the weir, so 4 in. for a 2 in. arm and 6 in. for a 3 in. arm.

Why? Right at the weir, water sheets over the top of the trap. Put the vent opening there and it gets gunked up fast.

The IPC fall rule nobody remembers

Length is only half of it on an IPC job. The total fall of the trap arm can't be more than one pipe diameter.

Say you've got a 2 in. arm running the full 8 ft at 1/4 in. per ft. That drops exactly 2 in., so you're good. Run that same 8 ft at 3/8 in. per ft and it drops 3 in. Now it fails, even though the length is fine.

One break in your favor: the IPC doesn't limit the trap arm on self-siphoning fixtures like toilets.

Don't vent below the weir

Both codes say the vent can't connect below the weir of the trap. Down there, the vent is past the water seal and can't protect it. Toilets get a pass on this one in both codes, since their trap outlet sits below the weir by design.

Cheat sheet

  • Measure from the trap weir to the vent
  • IPC is in feet, UPC is in inches
  • IPC: 5, 6, 8, 12, and 16 ft for 1 1/4 through 4 in. traps
  • UPC: 30, 42, 60, and 72 in. for 1 1/4 through 3 in. arms
  • UPC: the vent has to be at least 2x the pipe diameter from the weir
  • IPC: total fall can't be more than one pipe diameter
  • No venting below the weir, except toilets

Common questions

Where do you measure trap arm length from?

From the trap weir. On the IPC you measure to the vent fitting, and on the UPC to the inner edge of the vent.

How long can a 2 in. trap arm be?

8 ft at 1/4 in. per ft under the IPC. Under the UPC it's 60 in., which is 5 ft.

Do toilets have a trap arm limit?

Not under the IPC. Self-siphoning fixtures like toilets are left out of the trap arm table.