You need an expansion tank when the water system is closed. That happens when a check valve, backflow preventer, or pressure-reducing valve stops water from flowing back out to the main. Hot water expands, and in a closed system it's got nowhere to go.

The dead giveaway is a relief valve that drips after every heating cycle. Here's why that happens and what the codes want you to do about it.

Open vs closed systems

In an open system, that extra water from heating just pushes back into the main and nobody ever notices. Put a check valve, backflow preventer, or PRV on the service and that escape route is gone. Both codes call out those same devices as the ones that close a system.

That's how a house can go twenty years with zero problems, get a PRV put in, and have the relief valve start weeping within a week.

How much does water actually expand?

Not a lot, but water won't squeeze down. Heat a closed 80 gallon system from 50°F to 140°F and the water grows by about 1.34 gallons. With nowhere to go, the pressure climbs until the relief valve pops.

Heads up: A brand new, correctly rated relief valve that drips for a few minutes after each heating cycle and then stops is almost always thermal expansion, not a bad valve. Go look for a check valve, backflow preventer, or PRV on the service.

Don't just crank up the relief valve

Swapping in a relief valve set higher stops the drip, but it doesn't fix anything. The pressure still climbs every single cycle, and now everything in the house that's rated for the lower pressure is seeing more. Fix the actual problem with expansion control.

Where the tank goes

The tank has to be on the house side of the last device that closes the system. If there's a backflow preventer at the meter and a PRV after it, the tank goes after both.

Both codes put it on the cold side. The IPC spells it out: on the water heater cold supply, downstream of all check valves, PRVs, and backflow preventers.

Sizing, support, and precharge

  • Sizing: Neither code sizes the tank for you. Go by the manufacturer's instructions so the system stays under the 80 psi limit
  • Support: The IPC says you can't hang the tank off the pipe it's connected to. Support it from the structure
  • Precharge: Set the air charge to match the static cold water pressure right where the tank goes. A tank that ships at 40 psi going into a 62 psi system should get set to 62 psi

What about tankless heaters?

A tankless, on-demand heater barely holds any water, so there's barely any expansion. Neither code requires an expansion tank for one.

Cheat sheet

  • Check valves, backflow preventers, and PRVs make a system closed
  • Closed system plus a tank-type water heater means you need expansion control
  • Tank goes on the cold side, after every device that closes the system
  • Size it by the manufacturer, and support it from the structure
  • Precharge = static cold water pressure at the tank
  • Not needed for tankless heaters

Common questions

Why does my relief valve drip after the water heater runs?

Usually thermal expansion in a closed system. A check valve, backflow preventer, or PRV is keeping the extra water from going back to the main.

Does a tankless water heater need an expansion tank?

No. Neither code requires one for a tankless, on-demand heater.

What should I set the expansion tank pressure to?

The static cold water pressure right where the tank is going.