Quick version: a drainage fixture unit (dfu) is how much load a fixture puts on the drain. A water supply fixture unit (wsfu) is how much demand it puts on the water supply. They measure different things, so the same fixture has two different numbers.
Mixing them up is one of the most common sizing mistakes on the exam. Here's how to keep them straight.
What a dfu is
A dfu is basically a weight. It lets you add up a bunch of different fixtures to figure out the total load on a drain pipe, then size the pipe off the tables.
- Lavatory: 1 dfu
- Bathtub, with or without a shower over it: 2 dfu on the IPC
- Drinking fountain: 1/2 dfu on both codes
- Emergency floor drain: 0 dfu on both codes
What a wsfu is
A wsfu rolls together how much water a fixture uses, how fast, and how often. You add them up to get the demand on the supply piping, then convert that to gallons per minute.
Where the fixture is matters a lot here. On the IPC, a bathtub in a house is 1.4 wsfu total, but a public one is 4.0.
Why the numbers don't match
There's no formula to turn one into the other. They come from totally different things, and either one can be bigger. An IPC public flush tank toilet is 5.0 wsfu on the supply side and 4 dfu on the drain side.
What about things that run nonstop?
Fixture units assume not everything runs at the same time. Something that runs nonstop doesn't fit that.
On the drain side, both codes count 1 gpm as 2 dfu. So a sump pump pushing 15 gpm adds 30 dfu. On the supply side, something like a lawn sprinkler gets figured in gallons per minute and added on after you convert the fixture units.
You don't have to adjust for diversity
Double the fixture units and you don't double the gallons per minute. Not everything runs at once, and the bigger the group, the smaller the share running together. Both codes already built that into the tables, so you don't have to do it yourself.
There's also a hard floor. No matter what the math says, the pipe bringing water into the building can't be smaller than 3/4 in. on either code.
Cheat sheet
- DFU = load on the drain, WSFU = demand on the supply
- One fixture gets two separate numbers, and you can't convert between them
- Nonstop drain flow: 1 gpm = 2 dfu on both codes
- Diversity is already in the tables
- Water service into the building is never under 3/4 in.
Common questions
Are DFU and WSFU the same thing?
No. DFU is the load on the drain and WSFU is the demand on the water supply. Every fixture has a separate number for each.
How many DFU is 1 gpm?
Two. Both codes count 1 gpm of nonstop flow as 2 drainage fixture units.
How many DFU is a lavatory?
One.