Here's the difference in one line. An air gap ends above the flood level rim of the receptor. An air break ends below the flood level rim but above the trap seal.

You'll use both for indirect waste, where something drains into a floor sink, standpipe, or other receptor instead of tying straight into the drain. That one difference in height decides how well each one holds up when things back up.

What an air gap is

It's the open vertical space between the end of the waste pipe and the flood level rim of the receptor under it. It has to be wide open, just air, nothing in the way.

That last part trips people up. If a bracket, a strap, or a splash guard crosses that space, the gap doesn't count anymore, even if your tape measure says the distance is right.

What an air break is

An air break is when the pipe ends below the flood level rim of the receptor but above its trap seal. The pipe still isn't tied directly into the drain, it just sits lower.

Why the air gap wins

Think about what happens when the receptor backs up. Water rises to the rim and spills over onto the floor. An air gap sits above that point, so the dirty water never touches the pipe. An air break sits below the rim, so a backup can swallow the end of the pipe.

Neither one wears out, since they're just about where the pipe ends. The difference only shows up when something goes wrong downstream.

When you use each one

It comes down to how bad a backup would be. Clean water like AC condensate can use an air break. A food prep sink calls for an air gap, because contamination there is a real health problem.

How big does the air gap need to be?

On the IPC, the gap between an indirect waste pipe and the receptor's flood level rim has to be at least twice the effective opening of the pipe. So a 1 1/2 in. indirect waste needs at least 3 in.

Measure from the lowest edge of the pipe opening down to the flood level rim. If you measure from the center of the pipe, the gap looks bigger than it really is.

Heads up: A lot of plumbers leave a flat 1 in. gap out of habit. On the IPC the gap grows with the pipe. Twice the effective opening means a 1 1/2 in. pipe needs 3 in.

Cheat sheet

  • Air gap: ends above the flood level rim
  • Air break: ends below the flood level rim but above the trap seal
  • An air gap survives a backup, an air break can get swallowed
  • The gap has to be wide open, nothing crossing it
  • IPC indirect waste: air gap at least twice the effective opening

Common questions

Which is better, an air gap or an air break?

An air gap. It sits above the flood level rim, so a backed-up receptor can't reach the pipe.

Can AC condensate use an air break?

Yes. Clean water like coil condensate can drain through an air break.

How big is the air gap for indirect waste on the IPC?

At least twice the effective opening of the pipe. A 1 1/2 in. pipe needs 3 in.