An air admittance valve, or AAV, is a one-way valve. It lets air into the drain when the pressure drops, then closes so sewer gas can't get out. Whether you can actually use one comes down to your code.

The IPC has a whole section on them. The UPC doesn't mention them at all. Big difference, so let's go through both.

AAVs on the IPC

The IPC allows AAVs, but with strings attached. Individual and branch valves have to meet ASSE 1051, and stack-type valves meet ASSE 1050. Those two numbers are one digit apart, so they get swapped on the exam all the time.

  • Put the valve in after the drain and vent test, so the test doesn't wreck it or hide a leak
  • Individual and branch valves can only vent fixtures on the same floor that tie into a horizontal branch drain
  • Mount individual and branch valves at least 4 in. above the drain they're venting
  • Mount stack-type valves at least 6 in. above the flood level rim of the highest fixture
  • Keep any AAV at least 6 in. above insulation
Heads up for the exam: People swap these two heights all the time. It's 4 in. above the drain for individual and branch valves, and 6 in. above the highest flood level rim for stack-type valves.

It has to get air, and you have to reach it

Every AAV has to be accessible, and it has to be somewhere air can get to it. Seal one inside a cabinet with no opening and you've broken both rules.

This matters on service calls too. Fixture draining slow and the trap seal getting pulled down? The valve probably isn't letting air in. Smell sewer gas but everything drains fine? The valve probably isn't sealing. Either way, you need to get to it to swap it.

What an AAV can't do on the IPC

  • Replace every vent. At least one stack vent or vent stack per system still has to go outside
  • Sit in a supply or return air plenum
  • Vent a sump, unless an engineer designed that vent system
  • Go on an outdoor vent terminal just to get around the clearance to an air intake
  • Be the vent terminal on a drainage stack with more than six branch intervals

Why one vent still has to go outside

An AAV only lets air in. It can't let pressure out. If nothing in the system is open to the outdoors, that pressure has nowhere to go except right through your trap seals. That's why the IPC still wants at least one vent to open air.

AAVs on the UPC

Here's the short version: the UPC doesn't name them, define them, or reference them anywhere. And you can't just point to the IPC section to justify one.

The only way in is the UPC's alternate materials and methods section. The contractor has to send technical documentation to the Authority Having Jurisdiction showing it's equivalent, and it has to be approved before it goes in. That approval only counts in that jurisdiction, not the next town over.

Cheat sheet

  • IPC allows AAVs with conditions, the UPC has no AAV section
  • ASSE 1051 for individual and branch valves, ASSE 1050 for stack valves
  • Install after the DWV test, keep it accessible, and make sure it gets air
  • At least one vent per system still goes outside
  • Never in a plenum, and no AAV on a sump unless it's engineered

Common questions

Are air admittance valves up to code?

On the IPC, yes, with conditions. The UPC doesn't have a provision for them, so you'd need alternate approval from the Authority Having Jurisdiction.

Can I vent a whole house with AAVs?

No. On the IPC, at least one stack vent or vent stack in each system has to go outside.

How high does an AAV need to be?

On the IPC, individual and branch valves go at least 4 in. above the drain they vent. Stack-type valves go at least 6 in. above the highest fixture's flood level rim.