A wet vent is a pipe that's doing two jobs at once. It carries water from some fixtures and air for the others. You mostly see it in bathrooms, because it saves you from running a separate vent for every fixture.
Both codes allow it, but the rules are different enough that wet venting is one of the most missed topics on the exam. Here's what you need to know.
How it actually works
The dry vent ties in at one fixture, usually the one furthest upstream. After that point, the pipe is big enough that water runs along the bottom while air moves over the top. That open air space is what keeps the other traps from getting sucked dry.
Pretty much every wet venting rule is about keeping that air space open.
Rules both codes agree on
- Only bathroom group fixtures go on the wet vent
- Everything on the wet vent has to be on the same floor
- Only one wet-vented fixture can drain in upstream of the dry vent connection
- Anything else, like a kitchen sink, ties in downstream and gets vented the normal way
Wet venting on the IPC
The IPC is the more generous one. A horizontal wet vent can serve two bathroom groups on the same floor, and each fixture drain has to connect on its own. The IPC doesn't care what order things connect in, so the toilet can go anywhere along the branch.
Sizing comes from a table based on drainage fixture units: 1 dfu at 1 1/2 in., 4 dfu at 2 in., 6 dfu at 2 1/2 in., and 12 dfu at 3 in. The dry vent gets sized off the biggest pipe in the wet vent system.
Wet venting on the UPC
The UPC is tighter. You get one bathroom group on a horizontal wet vent, not two. And the toilet has to connect last, downstream of everything else.
Sizing is simpler, though. It's 2 in. for 4 dfu or less and 3 in. for 5 dfu or more. There's no 2 1/2 in. option at all. The dry vent gets sized off the total fixture units going into the wet vent.
The UPC also has a vertical wet vent, but it's pretty limited. It only takes trap arms from one and two fixture unit fixtures, it can serve up to four fixtures, and it maxes out at 6 ft of developed length.
Trap arms still count
Being on a wet vent doesn't get you out of the trap arm limits. Every fixture still has to meet the normal trap arm distance for your code. And the vent opening still can't sit below the trap weir, except for toilets.
Cheat sheet
- A wet vent carries water for some fixtures and air for the others
- Bathroom group fixtures only, all on the same floor
- Only one fixture can drain in upstream of the dry vent
- IPC: up to two bathroom groups, sized from a dfu table
- UPC: one bathroom group, toilet last, 2 in. up to 4 dfu and 3 in. for 5 dfu or more
Common questions
Can a kitchen sink go on a wet vent?
No. Only bathroom group fixtures can be on it. A kitchen sink ties in downstream and gets its own vent.
How many bathroom groups can share a horizontal wet vent?
Two on the IPC. Just one on the UPC.
Can a wet vent serve two floors?
No. On both codes, everything on the wet vent has to be on the same floor.